Measuring input:
- mV, mA, mA (also alternating quantities)
- various thermoelements and resistance thermometers
resistance variables
- frequency and pulse input (also for measuring the period)
- L-probe (oxygen measurement)
Measuring rate:
3 measurements / second
Output:
Short-circuit-proof analog output
e. g. 1 mV / °C or 0...10 Vdc (max 5 mA) or 0...20 mA or 4...20 mA
(max. load 10 Vdc) or according to customer specifikation (active current
limiting e.g. + 23 mA)
Pulse output for external counter
(e.g. as volume counter for flow volume)
Note: Only voltage values can be output if a thermoelement input
isdinearized.
Display:
4-digit, 7-segment display with sing
Digit height:
100 mm or 57 mm (optional)
Climate:
Storage: -10...+70 °C
Operation: 0...+60 °C |
Other features:
- active 2nd order filter for effective disturbance signal suppression;
(e.g. 50 Hz signal is reduced by more than 70 dB).
- end value (maybe zero or power adjustment) adjustable internally
- overflow indicator
Options:
- integrated shearing pin and compensating device in thermoelement
input
- linearization of thermoelements and Pt 100 resistance thermometers
- ac voltage and ac measurement by active rectifiers
- reciprocal display (display = 1 /input signal)
- magnifying function (e.g. 0...20 mA = display 800...1200 °C)
- calculation of one or two inputs (summation, difference formation,
multiplication, division, root extraction, logarithmizing, delogarithmizing)
- up to 2 limit values
Note: limit values internally adjustable
- Display mode:
|
- limit value 1, limit value 2 or
actual value selectable by internal switch
- load capacity of the contacts: 230 V / 6 A
- contacts as changeover contacts |
|